Aller au contenu
7.5 Élevée

CVE-2025-40944 A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET…

Description

A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state. This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.

Produits et versions touchés

Produit Versions touchées Corrigé en
SIMATIC ET 200AL IM 157-1 PN Versions non publiées
SIMATIC ET 200MP IM 155-5 PN HF 4.2 4.2.0 → dernières Pas de correctif indiqué
SIMATIC ET 200SP IM 155-6 MF HF Versions non publiées
SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) 1.3 premières → < 1.3 1.3
SIMATIC ET 200SP IM 155-6 PN R1 6.0 premières → < 6.0.1 6.0.1
SIMATIC ET 200SP IM 155-6 PN/2 HF 4.2 4.2.0 → < 4.2.5 4.2.5
SIMATIC ET 200SP IM 155-6 PN/3 HF 4.2 premières → < 4.2.2 4.2.2
SIMATIC PN/MF Coupler Versions non publiées
SIMATIC PN/PN Coupler 6.0 premières → < 6.0.0 6.0.0
Afficher les 6 autres branches
Produit Versions touchées Corrigé en
SIPLUS ET 200MP IM 155-5 PN HF 4.2 4.2.0 → dernières Pas de correctif indiqué
SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL 4.2 4.2.0 → dernières Pas de correctif indiqué
SIPLUS ET 200SP IM 155-6 PN HF 4.2 4.2.0 → < 4.2.5 4.2.5
SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL 4.2 4.2.0 → < 4.2.5 4.2.5
SIPLUS ET 200SP IM 155-6 PN HF TX RAIL 4.2 4.2.0 → < 4.2.5 4.2.5
SIPLUS NET PN/PN Coupler 6.0 premières → < 6.0.0 6.0.0