Non notée
CVE-2020-15787 A vulnerability has been identified in SIMATIC HMI Unified Comfort Panels (All versions <= V16)
Description
A vulnerability has been identified in SIMATIC HMI Unified Comfort Panels (All versions <= V16). Affected devices insufficiently validate authentication attempts as the information given can be truncated to match only a set number of characters versus the whole provided string. This could allow a remote attacker to discover user passwords and obtain access to the Sm@rt Server via a brute-force attack.
Produits et versions touchés
| Produit | Versions touchées | Corrigé en |
|---|---|---|
| SIMATIC HMI Unified Comfort Panels | Versions non publiées |
Références
- cert-portal.siemens.com cert-portal.siemens.com
Chronologie
- Publiée
- Dernière modification