Skip to content
7.5 High

CVE-2022-2277 Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP…

Description

Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP system. By default, ICCP is not configured and not enabled. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10.2 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*

Affected products and versions

Product Affected versions Fixed in
MicroSCADA X SYS600 10.3 10.3 → 10.3.1 No fix stated
MicroSCADA X SYS600 10.2 10.2 → 10.2.1 No fix stated
The 14 CVEs of MicroSCADA X SYS600 →