Skip to content
8.1 High

CVE-2021-35535 Insecure Boot Image vulnerability in Hitachi Energy Relion Relion 670/650/SAM600-IO series allows an attacker who…

Description

Insecure Boot Image vulnerability in Hitachi Energy Relion Relion 670/650/SAM600-IO series allows an attacker who manages to get access to the front network port and to cause a reboot sequences of the device may exploit the vulnerability, where there is a tiny time gap during the booting process where an older version of VxWorks is loaded prior to application firmware booting, could exploit the vulnerability in the older version of VxWorks and cause a denial-of-service on the product. This issue affects: Hitachi Energy Relion 670 Series 2.2.2 all revisions; 2.2.3 versions prior to 2.2.3.3. Hitachi Energy Relion 670/650 Series 2.2.0 all revisions; 2.2.4 all revisions. Hitachi Energy Relion 670/650/SAM600-IO 2.2.1 all revisions.

Affected products and versions

Product Affected versions Fixed in
Relion 670 Series 2.2 2.2.3 → < 2.2.3.3 2.2.3.3
Relion 670/650 Series Versions not published
Relion 670/650/SAM600-IO Versions not published
The 2 CVEs of Relion 670 Series →
Track this CVE