Skip to content
7.5 High

CVE-2018-16556 A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7…

Description

A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.

Affected products and versions

Product Affected versions Fixed in
SIMATIC S7-400 CPU 412-1 DP V7 Versions not published
SIMATIC S7-400 CPU 412-2 DP V7 Versions not published
SIMATIC S7-400 CPU 414-2 DP V7 Versions not published
SIMATIC S7-400 CPU 414-3 DP V7 Versions not published
SIMATIC S7-400 CPU 414-3 PN/DP V7 Versions not published
SIMATIC S7-400 CPU 414F-3 PN/DP V7 Versions not published
SIMATIC S7-400 CPU 416-2 DP V7 Versions not published
SIMATIC S7-400 CPU 416-3 DP V7 Versions not published
SIMATIC S7-400 CPU 416-3 PN/DP V7 Versions not published
Show the 24 other branches
Product Affected versions Fixed in
SIMATIC S7-400 CPU 416F-2 DP V7 Versions not published
SIMATIC S7-400 CPU 416F-3 PN/DP V7 Versions not published
SIMATIC S7-400 CPU 417-4 DP V7 Versions not published
SIMATIC S7-400 CPU 412-2 PN V7 Versions not published
SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) Versions not published
SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) Versions not published
SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) Versions not published
SIMATIC S7-410 CPU family (incl. SIPLUS variants) Versions not published
SIPLUS S7-400 CPU 414-3 PN/DP V7 Versions not published
SIPLUS S7-400 CPU 416-3 PN/DP V7 Versions not published
SIPLUS S7-400 CPU 416-3 V7 Versions not published
SIPLUS S7-400 CPU 417-4 V7 Versions not published
SIMATIC S7-400 CPU 412-1 DP V7 Versions not published
SIMATIC S7-400 CPU 412-2 DP V7 Versions not published
SIMATIC S7-400 CPU 414-2 DP V7 Versions not published
SIMATIC S7-400 CPU 414-3 DP V7 Versions not published
SIMATIC S7-400 CPU 414-3 PN/DP V7 Versions not published
SIMATIC S7-400 CPU 414F-3 PN/DP V7 Versions not published
SIMATIC S7-400 CPU 416-2 DP V7 Versions not published
SIMATIC S7-400 CPU 416-3 DP V7 Versions not published
SIMATIC S7-400 CPU 416-3 PN/DP V7 Versions not published
SIMATIC S7-400 CPU 416F-2 DP V7 Versions not published
SIMATIC S7-400 CPU 416F-3 PN/DP V7 Versions not published
SIMATIC S7-400 CPU 417-4 DP V7 Versions not published
The 3 CVEs of SIMATIC S7-400 CPU 412-1 DP V7 →
Track this CVE